Español(Spanish Formal International)

FUEL MANAGEMENT
FUEL SHIELD - Specification Sheet

General Data

Dimensions (L x l x p)

 300 x 100 x 160 mm (include filter)

Weights  

 2,8 kg (incl. filter)

 

 

Materials 

Flow Shield sensor

 

O-rings                

Viton®

Connectors

 Steel protection TAAC3, stainless steel, anodized

Casing

Combustion engines & burners

Mounting bracket

Stainless steel

   
Flow meter 
Measurement Principle                Volumetric, oscillating piston, with microprocessor
Measuring range 4 to 200 l/h
Accuracy better than 1 % of reading
Repeatability better than 0.2 % of reading
Admissible pressure - 1 to 6 bar
Mounting position  vertical
Operating temperature                -30 ...  90°C
Ingress protection Sensor and electronic, IP 68
   
Electrical Connection 
Power supply  8 - 28 VDC   
Pulse signal rectangular, duty cycle 50%
Pulse rate 80 ppl
 