FUEL MANAGEMENT FUEL SHIELD - Specification Sheet
| General Data |
|
Dimensions (L x l x p)
|
300 x 100 x 160 mm (include filter)
|
|
Weights
|
2,8 kg (incl. filter)
|
|
|
|
| Materials |
|
Flow Shield sensor
|
|
|
O-rings
|
Viton®
|
|
Connectors
|
Steel protection TAAC3, stainless steel, anodized
|
|
Casing
|
Combustion engines & burners
|
|
Mounting bracket
|
Stainless steel
|
| |
|
| Flow meter |
| Measurement Principle |
Volumetric, oscillating piston, with microprocessor |
| Measuring range |
4 to 200 l/h |
| Accuracy |
better than 1 % of reading |
| Repeatability |
better than 0.2 % of reading |
| Admissible pressure |
- 1 to 6 bar |
| Mounting position |
vertical |
| Operating temperature |
-30 ... 90°C |
| Ingress protection |
Sensor and electronic, IP 68 |
| |
|
| Electrical Connection |
| Power supply |
8 - 28 VDC |
| Pulse signal |
rectangular, duty cycle 50% |
| Pulse rate |
80 ppl |
|
|
|